Isolating and Safety Transformers for Screw and DIN Bar Installation

High-quality low voltage single-phase safety transformers with a protection degree of IP20, designed for use in DIN rail or floor screws installation.

Transformers for Screw & DIN Bar Installation image

Please note we are still adding products to our new website. Can't see the product you need? Contact us on 01444 243 452 / enquiries@gdrectifiers.co.uk

Expert technical support

Design Inspiration, whenever you need it

Custom & flexible ordering

Single Phase Isolating and Safety Transformers for Screw and DIN Bar Installation

Designed for DIN rail or floor screws installation

Meth Kft offers an impressive range of high quality low voltage single-phase safety transformers with a protection degree of IP20, designed for use in DIN rail or floor screws installation.

 

T1L

The T1L is a low voltage single-phase input isolating and safety transformer suitable for DIN rail or floor screws installation.

Rated Input Voltage: 230-400 ±V 

Rated Output Voltage: 2x115V or 2x115V

Rated Power: 50-400VA

Insulation Class: class F

Temperature Class: class B

Ambient Temperature: Ta=40°C

Protection Degree: IP 20

Test Voltage: 4.2KV/1’

Terminals: self-lifting screws

T1L Datasheet

 

Standards

–       CEI-EN 61558.2-4 and 2-6 – isolating and safety transformers

–       IEC 61558.2-4 and 2-6

 

T1L Technical Data

Part Number            Rated Power (VA)      Dimensions (mm)                Weight  

(Kg)  

Losses (W)       Efficiency (%)     Ucc (%)      ∆V (%)   
A B C D E no-load load
T1L-50 50 89 106 100 68.5 90 1.4 3.5 6.2 84 11.5 11.8
T1L-63 63 89 106 100 68.5 90 1.5 3.4 8.1 84.7 11.1 11.4
T1L-75 75 89 106 110 68.5 90 1.8 4.5 8.2 85.7 9.5 9.7
T1L-100 100 89 106 120 68.5 90 2.1 5.5 10.3 86.3 9.2 9.4
T1L-160 160 113 115 112 80 99 2.3 5.9 15 87.6 9 9.2
T1L-200 200 113 115 122 80 99 3 7.1 21.1 87.8 8.9 9.1
T1L-250 250 113 115 132 80 99 3.5 8.4 26.6 87.9 8.4 8.7
T1L-300 300 126 136 117 96 121 3.8 8.6 27 89.3 8.3 8.3
T1L-400 400 126 136 127 96 121 4.5 10.5 34.9 89.9 8.1 8.2

 

For further information on isolating and safety transformers for screw and DIN bar installation or to discuss your requirements, please call us on: 01444 243 452 or email: enquiries@gdrectifiers.co.uk.